The protection and management of MV/LV transformers in rural areas requires the use of specific circuit breakers adapted to significant load imbalances, and thus guarantees complete power usage even in unbalanced conditions. These devices (4 poles, three of which are protected) use air-break technology with chambers with metal partitions to cut the arc. Low voltage pole mounted circuit breaker D165T – D265T with a digital trip unit.
Pouduct Name
Circuit breaker Low voltage pole mounted circuit breaker D165T with digital trip unit
Description
The protection and management of MV / LV transformers in rural areas requires the use of specific Circuit Breakers adapted to significant load imbalances and thus guarantees the total use of the installed power even in unbalanced conditions. These devices (4 poles – 3 protected) use air-break technology with chambers with metal partitions to cut the arc
Benefits
1.Transformer protection (50 kVA or 100 kVA) more compact and easier to use than a fused solution
2.When the Circuit Breaker is closed, a spark gap limits the rise in potential of the LV neutral from the earth, for a value exceeding 10 kV
3.When the Circuit Breaker is open, an electrical connection is done between the neutral of the transformer and the ground
4.Contact us to define your needs (number of feeders, fixing support, type of rod assembly, Trip Unit type, Load Indicator option, etc.)
Pole Circuit Breaker
CIRCUIT B | REAKERS | |
D165T | D265T | |
Strandard | HN 63-S-11 | HN 63-S-11 |
Rated Voltage | 440 V | 440 V |
Rated Current | 165 A | 265 A |
Rated short-circuit breaking capacity Rated short-circuit making current | 4 000 A
6 800 A |
6 400 A
11 700 A |
Number of poles | 4 | 4 |
Number of outputs | 1 ouput | 2 outputs |
Cables cross-sections | 25 / 70 mm2 | 50 / 150 mm2 |
Rated power-frequency withstand voltage (50Hz – 1min) |
4 kV |
4 kV |
|
||
|
10 kV | 10 kV |
Rated lightning impulse withstand voltage (1.2/50µs) | 20 kV | 20 kV |
Control system | Manual | Manual |
Installation | Middle or Top pole | Middle or Top pole |
Digital Trip Unit
P = 50 kVA | P = 100 kVA |
Trip time |
P = 160 kVA |
Trip time |
|||||||||
U = 440 V | U = 440 V | U = 440 V | |||||||||||
I = 72,2 A | I = 144,3 A | I = 231 A | |||||||||||
Current in each phase (in A) | Current in each phase (in A) | Current in each phase (in A) | |||||||||||
1 | 2 | 3 | 1 | 2 | 3 | Min | Max | 1 | 2 | 3 | Min | Max | |
Temperature = + 20 °C | |||||||||||||
Initial load | 48 | 48 | 48 | 96 | 96 | 96 | 155 | 155 | 155 | ||||
Three-phases |
85 | 85 | 85 | 170 | 170 | 170 | 1 h 35 |
1 h 10 |
280 | 280 | 280 | 55 mn |
1 h 10 |
100 | 100 | 100 | 200 | 200 | 200 | 25 mn | 320 | 320 | 320 | 26 mn | |||
160 | 160 | 160 | 320 | 320 | 320 | 30 s | 6 mn | 500 | 500 | 500 | 30 s | 7 mn 30 s | |
balanced overload | 950 | 950 | 950 | 1900 | 1900 | 1900 | 0,02 s | 0,2 s | 3000 | 3000 | 3000 | 0,02 s | 0,1 s |
2000 |
2000 |
2000 |
4000 |
4000 |
4000 |
0,02 s |
0,05 s |
5640 | 5640 | 5640 | 0,015 s | 0,025 s | |
6400 | 6400 | 6400 | 0,015 s | 0,020 s | |||||||||
Three-phases |
58 | 58 | 120 | 116 | 116 | 240 | 1 h 50 |
50 mn |
185 | 185 | 400 | 32 mn |
33 mn |
58 | 58 | 160 | 116 | 116 | 320 | 15 mn | 185 | 185 | 500 | 11 mn | |||
unbalanced overload | 58 | 58 | 220 | 116 | 116 | 440 | 30 s | 7 mn | 185 | 185 | 700 | 30 s | 4 mn |
0 | 0 | 950 | 0 | 0 | 1900 | 0,02 s | 0,2 s | 0 | 0 | 3000 | 0,02 s | 0,1 s | |
Temperature = – 25 °C | |||||||||||||
Initial load | 76 | 76 | 76 | 152 | 152 | 152 | 240 | 240 | 240 | ||||
Three-phases | 110 | 110 | 110 | 220 | 220 | 220 | 1 h |
44 mn |
350 | 350 | 350 | 1 h |
45 mn |
balanced overload | 130 | 130 | 130 | 260 | 260 | 260 | 14 mn | 420 | 420 | 420 | 14 mn | ||
190 | 190 | 190 | 380 | 380 | 380 | 30 s | 5 mn | 600 | 600 | 600 | 30 s | 5 mn | |
Three-phases | 87 | 87 | 130 | 174 | 174 | 260 | 2 h 15 |
30 mn |
280 | 280 | 420 | 2 h 15 |
48 mn |
unbalanced overload | 87 | 87 | 180 | 174 | 174 | 360 | 10 mn | 280 | 280 | 560 | 13 mn | ||
87 | 87 | 240 | 174 | 174 | 480 | 30 s | 6 mn | 280 | 280 | 760 | 40 s | 5 mn 40 s | |
Temperature = + 50 °C | |||||||||||||
Initial load | 25 | 25 | 25 | 50 | 50 | 50 | 80 | 80 | 80 | ||||
Three-phases | 70 | 70 | 70 | 140 | 140 | 140 | 1 h 30 |
1 h 07 |
231 | 231 | 231 | 1 h 05 |
1 h 05 |
balanced overload | 90 | 90 | 90 | 180 | 180 | 180 | 20 mn | 300 | 300 | 300 | 17 mn | ||
160 | 160 | 160 | 320 | 320 | 320 | 45 s | 5 mn | 500 | 500 | 500 | 35 s | 5 mn 40 s | |
Three-phases | 48 | 48 | 100 | 96 | 96 | 200 | 1 h |
1 h |
155 | 155 | 320 | 1 h |
1 h |
unbalanced overload | 48 | 48 | 130 | 96 | 96 | 260 | 15 mn | 155 | 155 | 420 | 15 mn | ||
48 | 48 | 200 | 96 | 96 | 400 | 30 s | 7 mn | 155 | 155 | 650 | 30 s | 7 mn |